Description
DIN rail mounting transducers available in 55mm x 112mm or 100 x 112mm DIN rail cases
Application
Used to conver various inputs into standard DC signals for driving panel meters and for use in control devices.
Selection Guide
M100-TAP | Resistance measurement |
Typical Applications
The M100-TAP measures the value of resistance on tap position changers, typically used on high voltage transformers. Each position on the selector has an equal value of resistance so that as the tap position is increased or decreased the value of resistance increases or decreases respectively, The M100-TAP measure the value of this resistance and provides an output proportional to the value of the number of taps selected. The M100-TAP can also be used to measure variable resistance 2 or 3 wire systems.
Technical Specifications
INPUT | |
Rated Range | min 100 ohms ..max 20kOhms |
Sensor Current | min 50uA..max 10mA |
Sensor Voltage | < 1 Volt |
Working Range | 0-125% Rn |
OUTPUT | |
Rated value mA | 0-1/5/10/20 & 4-20mA |
Rated value volts | 0-5/10 & 1-5V |
ADJUSTMENT | |
Zero | ±2% |
Span | ±10% |
AUXILIARY | |
A.C. Voltage | 115/230/400V(±25% / 45-65Hz / 2VA) |
D.C. Voltage | 24/48/110V(±20% / galvanically isolated / <3W) |
WEIGHT&CASE SIZE | |
| Approx 0.4kg. 55mm case |
NOTE |
No isolation is provided between input and output |
Ordering Information
Product Code | No Taps | Output | Aux | Freq | Options |
M100-TAP | 10 | 5mA | 230V | 50Hz | |
Options
1 | Non standard Inputs/Outputs as far as technically viable |
2 | A.C. Auxiliary in range 57.7 to 450 volts |
3 | Calibration at temperature other than 23ºC |
A.C. Current Connection Diagrams