Tap Position Transducers

Description

DIN rail mounting transducers available in 55mm x 112mm or 100 x 112mm DIN rail cases

Application

Used to conver various inputs into standard DC signals for driving panel meters and for use in control devices.

Download PDF

Selection Guide

M100-TAPResistance measurement

Typical Applications

The M100-TAP measures the value of resistance on tap position changers, typically used on high voltage transformers. Each position on the selector has an equal value of resistance so that as the tap position is increased or decreased the value of resistance increases or decreases respectively, The M100-TAP measure the value of this resistance and provides an output proportional to the value of the number of taps selected. The M100-TAP can also be used to measure variable resistance 2 or 3 wire systems.

Technical Specifications

INPUT
Rated Rangemin 100 ohms ..max 20kOhms
Sensor Currentmin 50uA..max 10mA
Sensor Voltage< 1 Volt
Working Range0-125% Rn
OUTPUT
Rated value mA0-1/5/10/20 & 4-20mA
Rated value volts0-5/10 & 1-5V
ADJUSTMENT
Zero±2%
Span±10%
AUXILIARY
A.C. Voltage115/230/400V(±25% / 45-65Hz / 2VA)
D.C. Voltage24/48/110V(±20% / galvanically isolated / <3W)
WEIGHT&CASE SIZE
Approx 0.4kg. 55mm case
NOTE
No isolation is provided between input and output

Ordering Information

Product CodeNo TapsOutputAuxFreqOptions
M100-TAP105mA230V50Hz

Options

1Non standard Inputs/Outputs as far as technically viable
2A.C. Auxiliary in range 57.7 to 450 volts
3Calibration at temperature other than 23ºC

A.C. Current Connection Diagrams