Description
A range of low cost moulded case current transformers suitable for primary currents from 40A to 300A with built in sealable terminal covers
Application
For transforming various primary currents into 5A or 1A standard secondary using up to 21mm diameter cables.
Features
- Din rail mounting clip supplied
- Built in sealable terminal covers
- Mounting feet supplied
- Narrow width – 45mm
Technical Specification
- Conforms to IEC185, BS 7626, BSEN 60044-1, IEC 60044-1 and IEC 61869-2.
- Rated system voltage 0.72/3kV.
- Ambient temperature range -5°C to +50°C.
- Continuous current 1.2 x rated current.
Range
Class 3 | Class 1 | Class 0.5 | ||||||||||
VA | 1 | 1.5 | 2.5 | 5 | 1 | 1.5 | 2.5 | 5 | 1 | 1.5 | 2.5 | 5 |
40A | A1 | – | – | – | – | – | – | – | – | – | – | – |
50A | B1 | B2 | – | – | B5 | – | – | – | – | – | – | – |
60A | C1 | C2 | – | – | C5 | C6 | – | – | – | – | – | – |
75A | D1 | D2 | D3 | – | D5 | D6 | – | – | – | – | – | – |
80A | E1E2 | E3 | – | E5 | E6 | – | – | – | – | – | – | – |
100A | F1 | F2 | F3 | – | F5 | F6 | F7 | – | F9 | F10 | – | – |
120A | G1 | G2 | G3 | – | G5 | G6 | G7 | – | G9 | G10 | G11 | – |
150A | H1 | H2 | H3 | H4 | H5 | H6 | H7 | – | H9 | H10 | H11 | – |
200A | J1 | J2 | J3 | J4 | J5 | J6 | J7 | J8 | J9 | J10 | J11 | – |
250A | K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10 | K11 | K12 |
300A | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 | L9 | L10 | L11 | L12 |
1A secondary available by request.
Order Example: A moulded case current transformer type 13, with 5A secondary and 200A primary 2.5VA class 1 is part number 13-5-J7
Dimensions (mm)
Call us now on: +44 1922 640003