Description
DIN rail mounting transducers available in 55mm x 112mm or 100 x 112mm DIN rail cases
Application
Used to convert various inputs into standard DC signals for driving panel meters and for use in control devices.
Selection Guide
M100-XA1 | Single Phase |
M100-XA2 | 3 phase 3 wire balanced load |
M100-XA3 | 3 phase 4 wire balanced load |
M100-XA4 | 3 phase 3 wire unbalanced load |
M100-XA5 | 3 phase 4 wire unbalanced load |
M100-XA6 | 3 phase 3 wire balanced load externally connected |
| reverse C.T’s |
M100-XA7 | 3 phase 3 wire balanced load internally reversed C.T’s |
Typical Applications
The M100-XA series measure reactive power in single, 3 phase 3 or 4 wire balanced and unbalanced systems. Using the time division multiplier circuit means that they can be used over a wide range of input waveforms. The D.C. output signal is directly proportional to the instantaneous reactive power being measured.
Typical Applications include the measurement of reactive power in switchboards, power stations and generating sets etc. The high isolation of 4kV as with all M100 series allows these transducers to be connected to a variety of measuring and control devices and systems, such as analogue meters, PLC, computer systems, data loggers, digital instruments and telemetry systems.
Both auxiliary powered and self powered versions of each type are available. It is recommended to use an auxiliary powered version if the system being measured has voltage variations in excess of ±20%
Technical Specifications
INPUT | |
Rated value In: | 1 or 5 Amp C.T connected 0.5-10A direct connected |
Rated value Un: | 57.8 < 600 Volt |
Power Consumption | < 1VA voltage < 0.2VA current |
Working Range | 0-125%Un auxiliary powered 75%-125% Un self |
| powered 0-150% In |
Rated Frequency | 50 / 60 / 400Hz |
Frequency Influence | 0.005% / Hz |
Overload continuous | 4 x In 1.5 x Un |
Overload for 1 sec. | 50 x In 2 x Un |
OUTPUT | |
Rated value mA | 0-1/5/10/20&4-20mA |
Rated value volts | 0-5/10&1-5V |
ADJUSTMENT | |
Zero | ±2% |
Span | ±10% |
AUXILIARY | |
A.C. Voltage | 115 / 230 / 400V(±25%/45-65Hz/<2VA) |
D.C. Voltage | 24/48/110V(±20%/galvanically isolated/<3W) |
WEIGHT&CASE SIZE | |
M100-XA1,2,3,6,7 | Approx 0.6kg. 100mm case |
M100-XA4,5 | Approx 0.8kg. 100mm case |
Ordering Information
Product Code | IP In | Un | O/P | Range | Aux | Freq | Opt |
M100-XA4 | 400/5A | 400 | 0-20mA | 300kW | 120v | 50Hz | |
Options
1 | Non standard inputs / outputs as far as technically viable |
2 | A.C. Auxiliary in range 57.7 to 450 volts |
3 | Calibration at nominal Hz 35….450Hz |
4 | Calibration at temperature other than 23ºC |
A.C. Current Connection Diagrams