Description
DIN rail mounting transducers available in 55mm x 112mm or 100 x 112mm DIN rail cases
Application
Used to convert various inputs into standard DC signals for driving panel meters and for use in control devices.
Selection Guide
M100-FA1 | Self powered true zero outputs |
M100-FL1 | Auxiliary powered live zero outputs |
M100-FX1 | Auxiliary powered true zero outputs |
Typical Applications
The M100 series of frequency transducers are designed to measure frequency in single and 3 phase systems. The A.C. Input is converted to a D.C. output that is directly proportional to the change in input frequency within a specified span. The M100-FA1 is self powered (No auxiliary required). The working voltage range is 75% to 125% of the nominal voltage.
The M100-FL1 is auxiliary powered. The outputs are live zero, either 4mA or 1 volt. The auxiliary enables the working voltage range to be 15%-125% The M100-FX1 is essentially the same as the FA1 but an auxiliary is provided to enable the unit to have a working voltage range of 15%-125%. All types of the above frequency transducers are typically used to monitor and control frequency in such applications as 3 phase mains supplies, A.C. Generating sets and processing control etc.
Technical Specifications
INPUT | |
Rated Value Un | 57.8 << 600V |
Power Consumption | < 1VAÂ (FL1, FX1) < 1.5VA (FA1) |
Working Range | 75-125%Â Un(FA1)15-125%Un (FL1, FX1) |
Measuring Range | 45-55/45-65/55-65/360-440Hz |
Overload Continuous | 1.5 x Un |
Overload for 1 sec | 2 x Un (VA1 VA3) |
OUTPUT | |
Rated value mA | 0-1/5/10/20mA(FA1,FX1) |
Rated value mA | 4-20mA (FL1) |
Rated value volts | 0-5/10V(FA1,FX1) |
Rated value volts | 1-5V(FL1) |
ADJUSTMENT | |
Zero | No adjustment |
Span | No adjustment |
AUXILIARY | |
A.C. Voltage | 115/230/400V (± 25%/45-65Hz/<2VA) |
D.C. Voltage | 24/48/110V( ±20% / galvanically isolated |
| / < 3W) Note M100-FA1 is self powered |
WEIGHT&CASE SIZE | Approx 0.7kg. 100mm case |
Ordering Information
Product Code | Input In | Output | Aux | Freq | Options |
M100-VS1 | 110V ±15% | 20mA | – | 50Hz | |
Options
1 | Non standard inputs/outputs as far as technically viable. |
2 | A.C. Auxiliary in range 57.7 to 450 volts |
3 | Calibration at nominal Hz 35….450Hz |
4 | Calibration at temperature other than 23ºC |
A.C. Current Connection Diagrams