Taped Type current transformers

Taped Type CTs

Description

A range of Taped type current transformers suitable for primary currents from 1A-5000A with 1A or 5A secondaries. This standard range of measuring and protective current transformers is available as resin coated or tape wrapped.

Application

Suitable for measuring or protective applications with accuracies of class 0.2, 0.5, 1, 3, 5P10, 10P10 etc.

Features

  • Primary currents from 1A – 5000A.
  • Measuring or Protective types.
  • Base or busbar mounting.
  • Choice of sizes to customers specification.

Technical Specifications

  • Conforms to IEC44-1, IEC 185, BS7626 and IEC 61869-2.
  • Rated system voltage 0.72/3kV.
  • Ambient temperature range -5°C to +50°C.
  • Frequency range 50-60Hz (400Hz available on request).
  • Insulation level, 3kV (50Hz) for 1 minute.
  • Continuous current, 1.2 x rated current.
  • Short-term thermal current (Ith), 60 x rated current.
  • Dynamic current (Idyn), 2.5 x Ith.

Test Certificates

Our production facilities allow automated printing of test cetificates for individual current transformers, if requested.

Terminal Covers

Ring type current transformers can be provided with sealable terminal covers. Please specify on your order if required.

Burden

When choosing the VA of a current transformer, the burden of the instrument should be taken into account. For example, moving iron panel meters require a VA of less than 2.5 .
Where possible the instrument is remote from the CT, the VA imposed by the length of the connection wires should be taken into consideration.
The graph opposite outlines the effect of connection wire length on VA.

Multiple Primary Terms

The ratio of a current transformer can be reduced by passing more than one conductor turn through the centre of the CT. The ratio will therefore be the CT primary divided by the number of turns.
For example: a 400/5 CT with 2 primary turns passing through of 200A conductor will give you 400/5, like wise.