CTV127L Moulded Case Current Transformers (ANSI/IEEE spec)

Description

Compact moulded case current transformers from 400 – 3500A with UL recognition and a 127x54mm window (5” x 2.13”).

Application

For transforming various primary currents into 1A or 5A secondary.

Technical specification

  • 600V, 10KV BIL to IEEE C57.13
  • Built in sealable terminal covers
  • Built in busbar mounting
  • 127mm x 54mm window (5” x 2.13”)
  • Polycarbonate case material
  • Terminal Torque: 0.9Nm
  • Bus clamp Torque: 0.2Nm

Dimensions

Range

60HzBurdenB0.1B0.2B0.5B0.9B1.8RF @30°


2.5VA5VA12.5VA22.5VA45VA 
Part NumberPrimarySec





CTV127L400/5-ANSI-UL40051.21.22.4  1
CTV127L500/5-ANSI-UL50051.21.22.4  1
CTV127L600/5-ANSI-UL60050.31.22.42.4 1
CTV127L750/5-ANSI-UL75050.30.61.22.42.41
CTV127L1000/5-ANSI-UL100050.30.60.61.21.21
CTV127L1200/5-ANSI-UL120050.30.30.60.61.21
CTV127L1500/5-ANSI-UL150050.30.30.30.60.61
CTV127L1600/5-ANSI-UL160050.30.30.30.60.61
CTV127L2000/5-ANSI-UL200050.30.30.30.30.61
CTV127L2500/5-ANSI-UL250050.30.30.30.30.61
CTV127L3000/5-ANSI-UL300050.30.30.30.30.31
CTV127L3200/5-ANSI-UL320050.30.30.30.30.31
CTV127L3500/5-ANSI-UL350050.30.30.30.30.31

Mag Curve

Call us now on: +44 1922 640003