Series 162,
20mm Busbars
Posted

Description

A range of compact moulded case current transformers suitable for primary currents from 30A to 250A with built in terminal covers.

Application

For transforming various primary currents into 1A or 5A secondary using 20x10mm busbars or 20mm diameter cables.

PDF

Features

  • Built in sealable terminal covers.
  • Mounting feet and busbar screws supplied.
  • Narrow width – 60mm.
  • Din rail clip supplied with CT162 only.

 Technical Specification

  • Conforms to IEC185, BS 7626, BSEN 60044-1,
  • IEC 60044-1, BSEN 61869-2 and IEC 61892-2.
  • Rated system voltage 0.72/3kV.
  • Ambient temperature range -5°C to +50°C.
  • Continuous current, 1.2 x rated current.

RANGE (Type 162) 5A Secondry

Class 3 Class 1 Class 0.5
VA 1 1.5 2.5 5 1 1.5 2.5 5 1 1.5 2.5 5
30A A1
40A B1 B2
50A C1 C2 C5
60A D1 D2 D5
80A E1 E2 E3 E4 E5 E6 E7
100A F1 F2 F3 F4 F5 F6 F7 F9
120A G1 G2 G3 G4 G5 G6 G7 G8 G9 G10 G11
150A H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12
200A J1 J2 J3 J4 J5 J6 J7 J8 J9 J10 J11 J12
250A K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12

 RANGE (Type 162D) 5A Secondry

Class 1 Class 0.5 Class 0.55 Class 0.2 Class 0.25
VA 2.5 5 10 2.5 5 10 1.5 2.5 5 1.5 2.5 5 1.5 2.5 5
30A A1
40A B1
50A C1 C4 C5 C7 C8 C10
60A D1 D4 D7 D8 D10 D11
80A E1 E2 E4 E7 E8 E10 E11 E13 E14
100A F1 F2 F3 F4 F5 F7 F8 F9 F10 F11
150A G1 G2 G3 G4 G5 G6 G7 G8 G9 G10 G11 G12 G13 G14 G15
200A H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 H13 H14 H15
250A J1 J2 J3 J4 J5 J6 J7 J8 J9 J10 J11 J12 J13 J14 J15
1A secondary available by request.
Order Example: A moulded case current transformer type 162, with 5A secondary and 100A primary 5VA class 1 is part number 162-5-F8

DIMENSIONS (mm)

162 162D dimension diagram