Description
DIN rail mounting transducers available in 55mm x 112mm or 100 x 112mm DIN rail cases
Application
Used to convert various inputs into standard DC signals for driving panel meters and for use in control devices.
Selection Guide
| M100-RTD | RTD temperature measurement |
Typical Applications
The M100-RTD monitors the resistance of either 100 Ohm platinum or 120 Ohm Nickel. The RTDs resistance increase as the temperature rises, this resistance change is detected by the M100-RTD, which provides an output corresponding to the temperature being measured. The temperature versus resistance values are provided by the supplier of the RTD used.Â
RTD measurement of temperature is used in large transformers and large motors to ensure winding temperatures do not rise to a level that would change the winding.
Technical Specifications
| INPUT | |
| 2 or 3 wire input | |
| Platinum Pt 100 Ohm RTD | min. span 20 Ohms…max |
| span 200 Ohms |
| Nickel Ni 120 Ohm RTD | min. span 24 Ohms…max |
| span 240 Ohms |
| OUPUT | |
| Rated value mA | 0-1 / 5 / 10 / 20 & 4-20mA |
| Rated value volts | 0-5 / 10 & 1-5V |
| ACCURACY | Class ±0.5% |
| ADJUSTMENT | |
| Zero | ±2% |
| Span | ±10% |
| AUXILIARY | |
| A.C. Voltage | 115 / 230 / 400V(±25% / 45-65 |
| Hz / <2VA) |
| D.C. Voltage | 24/48/110V(±20% / |
| galvanically isolated / <3W) |
| WEIGHT&CASE SIZE | |
| Approx 0.3kg. 55mm case |
NOTE | |
Ordering Information
| Product Code | RTD | Temp | O/p | Aux | Freq | Options |
| M100-RTD | Pt100 | 0-250ºC | 5mA | 230v | 50Hz | |
Options
| 1 | Non standard inputs/outputs as far as technically viable |
| 2 | A.C. Auxiliary in range 57.7 to 450 volts |
| 3 | Calibration at temperature other than 23ºC |
A.C. Current Connection Diagrams