RTD Temperature Transducers

RTD TEMPERATURE TRANSDUCERS

Description

DIN rail mounting transducers available in 55mm x 112mm or 100 x 112mm DIN  rail cases

Application

Used to convert various inputs into standard DC signals for driving panel meters and for use in control devices.

Download PDF

Selection Guide

M100-RTDRTD temperature measurement

Typical Applications

The M100-RTD monitors the resistance of either 100 Ohm platinum or 120 Ohm Nickel. The RTDs resistance increase as the temperature rises, this resistance change is detected by the M100-RTD, which provides an output corresponding to the temperature being measured. The temperature versus resistance values are provided by the supplier of the RTD used.Â

RTD measurement of temperature is used in large transformers and large motors to ensure winding temperatures do not rise to a level that would change the winding.

Technical Specifications

INPUT
2 or 3 wire input
Platinum Pt 100 Ohm RTDmin. span 20 Ohms…max
span 200 Ohms
Nickel Ni 120 Ohm RTDmin. span 24 Ohms…max
span 240 Ohms
OUPUT
Rated value mA0-1 / 5 / 10 / 20 & 4-20mA
Rated value volts0-5 / 10 & 1-5V
ACCURACYClass ±0.5%
ADJUSTMENT
Zero±2%
Span±10%
AUXILIARY
A.C. Voltage115 / 230 / 400V(±25% / 45-65
Hz / <2VA)
D.C. Voltage24/48/110V(±20% /
galvanically isolated / <3W)
WEIGHT&CASE SIZE
Approx 0.3kg. 55mm case

NOTE

Ordering Information

Product CodeRTDTempO/pAuxFreqOptions
M100-RTDPt1000-250ºC5mA230v50Hz

Options

1Non standard inputs/outputs as far as technically viable
2A.C. Auxiliary in range 57.7 to 450 volts
3Calibration at temperature other than 23ºC