Description
DIN rail mounting protection relays for use in single and three phase systems. Available in 55mm x 112mm or 100 x 112mm DIN rail cases
Application
For over protection, under protection and combined under & over protection available in AC current AC voltage & frequency versions. Millivolt trip, DC voltage trip, Reverse Power, Phase sequence & Phase balance relays also available in our extensive range of protection relays..
Selection Guide
M200-V1U | Single phase under voltage |
M200-V1O | Single phase over voltage |
M200-V1C | Single phase combined voltage |
M200-V33U | 3 phase 3 wire under voltage |
M200-V33O | 3 phase 3 wire over voltage |
M200-V33C | 3 phase 3 wire combined voltage |
M200-V34U | 3 phase 4 wire under voltage |
M200-V34O | 3 phase 4 wire over voltage |
M200-V34C | 3 phase 4 wire combined voltage |
Typical Applications
The M200 AC voltage protection relay provides voltage monitoring and protection in both single and 3 phase systems. Used in applications such as mains failure, regulation of power supplies and to protect voltage sensitive equipment. Under, over and combined over/under units are available. The relay operates when the externally adjustable trip point is reached.
An external differential control is provided with adjustment 1-15%. The differential ensures that the parameter being measured returns to % set above or below (depending on whether it is an under or over unit) the trip point before the relay returns to its original state. As is common with all the M200 relays, on over units the relay energises when the input signal exceeds the trip point. On under units the relay de-energises when the input signal exceeds the trip point. A red LED indicates the state of the relay whilst a green LED indicates the condition of the power supply.
Technical Specifications
INPUT | |
Rated value Un: | Single phase 57.8 < 500V three phase 100<500V |
Frequency: | 50, 60 or 400Hz |
Burden | <2.5VA per phase single units |
Burden | <3VA per phase combined units |
Overload | 1.5 x Un continuous 2 x Un for 3 seconds |
SETPOINT | |
Range under | Adjustable 75% to 100% Un |
Range Over | Adjustable 100% to 125% Un |
Repeatability | Better than 0.5% of full span |
Differential | Adjustable 1 to 15% |
Operating time | Typically 200mS |
AUXILIARY | All units self powered |
WEIGHT&CASE SIZE | |
Single Units | Approx 0.4kg. 55mm case |
Combined Units | Approx 0.6kg. 100mm case |
Ordering Information
Product Code | Input | Freq | Option |
M200-V34U/D | 230V | 50V | 5 Sec t/d |
- On all the above units an internally set time delay is available for any value between 1 & 10 seconds. To order use the above codes, adding a D at the end of the code. e.g. M200-V34U/D 5 seconds (state the fixed delay period).
- To prevent nuisance tripping when there is a slight variation in the voltage supply the following option is available. The external differential is replaced on the following products with an externally customer adjustable time delay. On these units the time delay is adjustable from 200mS to 10 seconds and the differential is fixed at 1%.
M200-V1X: Single phase under voltage
M200-V1Y: Single phase over voltage
M200-V1W: Single phase combined voltage
M200-V33X: 3 phase 3 wire under voltage
M200-V33Y: 3 phase 3 wire over voltage
M200-V34X: 3 phase 4 wire under voltage
M200-V34Y: 3 phase 4 wire over voltage
M200-V34W: 3 phase 4 wire combined voltage
3. Calibration at temperature other than 23ÂșC
Connection Diagrams
Call us now on: +44 1922 640003