M560 Powersig Transducers

M560 Powersig Transducers

Description

DIN Rail mounting multifunction transducers supplied in 100 x 112mm DIN rail cases.

The M560 PowerSig is a complete 1 phase or 3 phase multifunction AC power transducer with 3 analogue outputs

Application

Self contained measurement of a wide range of electrical paremeters, where communication options are required

Analogue Outputs

Upto 3 fully isolated outputs are available. Most of the parameters measured can be assigned to the outputs. Outputs can be either DC mA or DC volts. If PowerSig is purchased without the option of RS485 the user must specify which parameter is required for each output when ordering.

Options

RS485 Output – This is auto configurable and set up software is provided.
Pulsed Output – This can be assigned to Wh, Varh, Ah or Vah

ModelDetails

M560-AT1: Single Phase

M560-AT1-3:Single Phase 3 wire

M560-AT4: 3 Phase 3 wire Unbalanced Load

M560-AT9: 3 Phase 4 wire Unbalanced Load

DC Auxiliary
If RS485 output is not required. The customer should specify which parameter is required for analogue outputs, CT ratios, VT ratios, pulse duration etc. These can be programmed by out factory before despatch.

Ordering Information

Information RequiredExample
Product CodeM560-AT9
Nominal Input Voltage230 L/N
Nominal Input Current5A AC
System Frequency50Hz
Auxiliary230V AC
Output3 x 4-20mA
OptionRS485 Modbus

Specifications

ACCURACYINPUT
Specified @ 23ºC 10%-Un 10%-lnRated Un: Direct connected voltages between 57.8 and 600V. Specify Nominal
Paremeters unless stated: Class 0.3% to IEC 688Range: 2-120% Un
Volts and Amps: Class 0.25% to IEC 688Overload 1.5 x Un cont. 4 x Un for 1 sec
Frequency: Class: 0.1Hz o IEC 688Rated In: 1 or 5 Amp
Power Factor: Class: 1.0% to IEC 688Range 2-120% In
Active and Reactive Energy: 1% of reading IEC 1036Burden: 0.5VA per phase Volts & Amps
Overload: 4 x In continous. 50 x In for 1 sec
Frequency 50/60Hz Nominal range 45/65Hz
ANALOGUE OUTPUTSAPPLIED STANDARDS
3 Outputs: Programmable to any 3 parameters (Apart from energy measurements)General: IEC688 BSEN60688, BS4889, IEC359.
Rated value: Specified @ 20mAEMC:
0-1mA into < 10 kOhm loadEmmisions: BSEN50081/1
0-5mA into < 2 kOhm loadImmunity BSEN50082/2
0-10mA into < 1 kOhm loadSafety: IEC 1010, BSEN601010
0-20mA into < 0.5 kOhm load
4-20mA into < 0.5 kOhm load
0-10 volts > 1 kOhm load
INSULATION
Test voltage:4kV RMS 50 Hz for 1 min
Inputs / Case / Auxiliary / Output
3kV RS485 / Outputs
1.5kV relay
1kV between Outputs
Impulse Test:EMC 5kV transient coplies with IEC801/ EN55020 HF
Surge Withstand:IEC801/EN55020 Ansi C37.90A
Interference:EHF 2.5kV 1Mhz complying to IEC255-4
Protective class II:Complying to IEC348
ENVIRONMENTAPPROVALS
Working temp: 0 – +60ºCUL C-UL CSA
Storage temp: -30 – 65ºC
Temp coefficient: 0.01% per ºC
AUXILIARY
AC voltage 115 or 230 or 277 volts (± 15%)
DC voltage 12 / 24 / 48 / 110 / 125 volts (± 15%)

Case Dimensions

Connection Diagrams

Call us now on: +44 1922 640003