General Specifications

General Specifications

Environmental

Working Temperature0 to +60 deg C
Functional Temperature-25 to +70 deg C
Storage Temperature-40 to 85 deg C
Temperature Coefficient0.02% per deg (200 ppm/ºC)
Relative Humidity95% non condensing
Class of ClimateHSE complying with DIN 40040
-3 complying with VDE/VDI 3540

Relay output

Relay Typedual pole change over
MaterialSilver / Candium
Contact Resistance200mOhm max typically < 50mOhm
Rating AC:250V 10A
Rating DC150V 10A
Electrical Life1 x 105 at above load
Mechanical Life5 x 106
Operating time approx7mS (20mS max)
Dielectric strengthBetween coil and contacts
5kV RMS 1min
Between Adjacent contacts
1kV RMS 1min
Insulation resistance1000M Ohm at 500V DC
Operating temperature-30 to +75 deg C
Approval UL and CSA recognised

Insulation

Test Voltage4kV RMS 50Hz 1 min between Input/Case/Auxiliary
Impulse TestEMC 5kV transient complying with IEC 801 /
EN55020
HF interference testEHF 2.5kV 1MHz complying with IEC 255-4
Protection ClassII complying with IEV 348

Applied Standards

GeneralIEC 144 / BS 5420 / VDE / VDI0435 / IEC 947
/ EN6094
Safety IEC 348 / BS4753 DIN 57411 / VDE 0411
ANSI C37
Surge withstandIEC 801 / EN 55020 ANSI C37-90A
Radio ScreeningRFI degree N complies with VDE 0875
VDE 0875

Enclosures & Approvals

FixingSnap on to DIN rail 35mm x 7.5mm complies with
DIN-EN 50022 BS5584
MountingAny position
Enclosure codeCase IP 50 / terminals IP 30. Complies with
IEC 529 BS5490 DIN 40050
U.L.ApprovalFile No E157034

Enclosures & Approvals

Call us now on: +44 1922 640003