Earth Leakage Relays

Earth Leakage Relays
Posted

Description

Variable Earth Leakage Relays in compact 35mm din rail mounting cases for use on 3 phase electrical systems.

Application

To monitor earth leakage current and to operate an associated relay at a preset current. May be used to shut down a system or operate an alarm under fault conditions.

Product

Part numberSensitivityTime DelayFrequencyVoltage
RCR-V3030mA-30A0-10 Seconds50/60Hz115/230V AC
RCR-V30-400V30mA – 30A0-10 Seconds50/60Hz400V AC
RCR-V30-60V DC30mA – 30A0-10 Seconds50/60Hz10-60V DC
ELR’s are fitted with test and reset buttons. Pressing the test button allows a fault to be simulated and the output relays operate accordingly. Pressing the reset button after a fault occurs restores the unit back to its normal operation. A red LED light will illuminate after the unit trips due to an excessive fault current.

Dimensions

Specifications

Supply Voltage (Un):24, 115/230, 400V AC (85-115%) 12-125V DC (85-110%) 10-60V DC(90-110%)
Power Consumption6VA
Ambient Temperature-20ºC to +55ºC
Relative Humidity+95%
HousingUL94VO Flame Retardent
Weight200g
Mounting35mm Din Rail
Terminal Conducter≤ 2.5mm² stranded

≤ 4mm² solid

Output1 x SPNO relay

1 x SPDT relay

Terminal Protection:IP20
Approvals:IEC 60755, 60947, 62020, 61543
N.B.
210MM toroids should not be used for sensitivity settings of less than 300mA

Connections Diagrams