Synchronysing Check Protection Relay |

Selection Guide |
| M200-PLL | 1 generator 1 bus or 2 generators |
| M200-PLD | 1 generator 1 bus with dead bus facility |
| Both units can be used on single or 3 phase systems. | |
Typical Applications |
| The M200-PLL & PLD are synchronised check relays, also known as paralleling relays. They are used to ensure that two AC supplies are synchronised, frequency, phase angle and voltage have to be within preset limits. The M200-PLL can monitor either main bus bar and incoming generator, or two generators. The PLL has customer adjustment of the vifferential voltage of between 10 to 30%. This voltage corresponds to 6 to 20 electrical degrees. The unit compares the input voltage and phase relationship of the bus bar as to that of the generator, when the signal is within preset limits, the relay energises. The M200-PLD operates as the M200-PLL but has the additional feature of the dead bus facility. This enables the relay to energise with a generator supply only, which is a common requirement where mains failure occurs. |
Technical Specification |
| INPUT | |
| Rated value Un: | 57.8 < 500V ±25% |
| Frequency: | 50 / 60 / 400Hz |
| Burden: | < 4VA terminals marked GEN<2VA terminals marked BUS |
| Overload: | 1.5 x continuous 10 x Un for 3 seconds |
| SETPOINT | |
| Range: | Adjustable 10% to 30% of nominal system voltage (6-20 electrical degrees) |
| Repeatability: | Better than 0.5% of span |
| Differential: | Fixed at 5% |
| Operating time: | Typically 500mS |
| AUXILIARY | |
| Both units are self powered | |
| WEIGHT&CASE | Approx 0.6kg. 100mm case |
Ordering Information |
| Product Code | System Voltage | Frequency | Options |
| M200-PLD | 400V | 50Hz | Cal at 35șC |
Options |
| 1 | Calibration at temperature other than 23șC |
Data Sheet in PDF Format Available here
Contact sales: sales@hobut.co.uk