Thermistor Trip |

Selection Guide |
| M200-TTA | Automatic reset |
| M200-TTM | Manual reset |
Typical Applications |
| The M200 thermistor trip accepts positive temperature coefficient inputs. Typically used to monitor temperature in motor windings. When the thermistor is below its predetermined temperature the resistance is low and the M200-TTA/TTM relay is energised. A green LED indicates the safe condition. When the temperature exceeds the predetermined temperature the resistance of the thermistor rapidly increases, this increase in temperature is detected by M200-TTA/TTM and the relay is de-energised. The M200-TTM is manually set, once the relay has de-energised it will stay de-energised regardless of the temperature being monitored. The relay can only be reset via the reset push button on the front of the unit. The M200-TTA automatically resets once the temperature has dropped below the trip point. A yellow LED is provided to indicate the condition of the power supply. |
Technical Specification |
| INPUT | |
| Positive temperature coefficient thermistors: | Sensors can be connected in series but 1500Ohms must not be exceeded |
| Trip Point | 2500-3500 Ohm |
| Reset Point | 1500-2300 Ohm |
| Total resistance of sensor loop | 1500 Ohms max at nominal temperature |
| Differential | Fixed 5% |
| Repeatability | Beter than 5% |
| RESET | |
| M200-TTA | Automatic |
| M200-TTM | Manual via push switch on front of product |
| AUXILIARY | |
| A.C. Voltage | 115/230/400V±25%/45-65Hz/2VA |
| D.C. Voltage | 24 volt(±20% / non-isolated)< 3 watt |
| WEIGHT&CASE | |
| Approx 0.3kg. 55mm case |
Ordering Information |
| Product Code | Aux | Freq | Option |
| M200-TTA | 230V | 50Hz |
Options |
| 1 | A.C. auxiliary in range 57.7 to 480 volts |
| 2 | Calibration at temperature other than 23ºC |