Reverse Power Protection Relay

reverse power protection relay

Selection Guide

M200-RP1 Single or 3 phase 4 wire
M200-RP3 3 phase 3 wire

Typical Applications

The M200 reverse power relay is used to monitor the direction of power from A.C generators, if the current in the system being monitored is reversed, to a value greater than the customer adjustable preset limit the relay will energise. The adjustable trip point is 2% to 20% of input  current. An adjustable time delay of 0 to 20 seconds is crovided. Correct setting of the trip point and time delay, will ensure protection agaisnt motoring in the event of a generator failure and prevent tripping due to transients encountered during synchronisation. A red LED indicates the state of the relay and a green LED indicates the condition of the power supply.

Technical Specification

INPUT  
Rated value Un 57.8< 500V ±25%
Rated value In C.T. operated 1 or 5A or direct connected 0.2 to 10A
Frequency 50/60/400Hz
Burden <3VA voltage <0.5VA current
Overload 1.5 x Un 2 x In continuous 2 x Un 10 x In for 3 seconds
SETPOINT  
Repeatability Better than 0.5% of full span
Time delay Adjustable 200mS to 20 sec
Hysteresis 1%
AUXILIARY  
All units self powered  
WEIGHT&CASE Approx 0.6kg. 100mm case

Ordering Information

Product Code In Input Un Input Freq Options
M200-RP3 1 Amp 400 Volt 50Hz 5 sec T/D

Options

1 Adjustable time delay max 30 seconds
2 A.C. Auxiliary in range 57.7 to 480 volts
3 Calibration at nominal Hz 35...450Hz
4 Calibration at temperature other than 23șC

Connection Diagrams

 

Data Sheet in PDF Format Available here

Contact sales: sales@hobut.co.uk