Reverse Power Protection Relay |

Selection Guide |
| M200-RP1 | Single or 3 phase 4 wire |
| M200-RP3 | 3 phase 3 wire |
Typical Applications |
| The M200 reverse power relay is used to monitor the direction of power from A.C generators, if the current in the system being monitored is reversed, to a value greater than the customer adjustable preset limit the relay will energise. The adjustable trip point is 2% to 20% of input current. An adjustable time delay of 0 to 20 seconds is crovided. Correct setting of the trip point and time delay, will ensure protection agaisnt motoring in the event of a generator failure and prevent tripping due to transients encountered during synchronisation. A red LED indicates the state of the relay and a green LED indicates the condition of the power supply. |
Technical Specification |
| INPUT | |
| Rated value Un | 57.8< 500V ±25% |
| Rated value In | C.T. operated 1 or 5A or direct connected 0.2 to 10A |
| Frequency | 50/60/400Hz |
| Burden | <3VA voltage <0.5VA current |
| Overload | 1.5 x Un 2 x In continuous 2 x Un 10 x In for 3 seconds |
| SETPOINT | |
| Repeatability | Better than 0.5% of full span |
| Time delay | Adjustable 200mS to 20 sec |
| Hysteresis | 1% |
| AUXILIARY | |
| All units self powered | |
| WEIGHT&CASE | Approx 0.6kg. 100mm case |
Ordering Information |
| Product Code | In Input | Un Input | Freq | Options |
| M200-RP3 | 1 Amp | 400 Volt | 50Hz | 5 sec T/D |
Options |
| 1 | Adjustable time delay max 30 seconds |
| 2 | A.C. Auxiliary in range 57.7 to 480 volts |
| 3 | Calibration at nominal Hz 35...450Hz |
| 4 | Calibration at temperature other than 23șC |
Data Sheet in PDF Format Available here
Contact sales: sales@hobut.co.uk