Phase Balance Protection Relay |

Selection Guide |
| M200-PB1 | Detects phase loss & phase unbalance |
| M200-PB2 | Detects phase loss, phase imbalance & symmetrical undervoltage |
Typical Applications |
| The M200-PB1 can detect the following conditions in 3 phase 3 or 4 wire systems. Phase unbalance, Phase loss, Phase Reversal, Phase Sequence. The phase balance relays are used to detect phase loss and unbalance in systems using motors, generators, heater elements, transformers etc. A phase unbalance as small as 10% in a 3 phase motor can cause the temperature in the motor winding to increase by more than 120%, correct setting of the PB1/PB2 will ensure that this does not occur. Protection against open phase regenerated voltage created if a single phase should fail is also provided. Customer adjustment of unbalanced voltage between 5 to 15% is provided along with time delay adjustment of 200mS to 10 seconds. If the system being monitored is healthy, the relay is energised, red LED illuminated, if there is a phase unbalance greater than the preset level or phase loss/reversal occurs, the relay de-energises after the time delay period. The M200-PB2 provides all the protection features of the PB1 with the additional benefit of having symmetrical under voltage protectgion. This means that if all 3 phase voltages remain balanced, but drop below a preset voltage, the relay will de-energise. The under voltage is internally set, for standard units it is set at 85% below the nominal voltage but this value can optionally be between 70 and 90%. |
Technical Specification |
| INPUT | |
| Rated value Un | 57.8 < 500V ±25% |
| Frequency | 50 / 60 / 400Hz |
| Burden | <2VA |
| Overload | 1.5 x Un 2 x Un |
| SETPOINT | |
| Range | Adjustment 5% to 15% unbalanced voltage |
| Repeatability | Better than 0.5% of full span. |
| Undervoltage | PB2 only, preset 85% of nominal voltage |
| (optional 90% to 70%) | |
| Time delay | Adjustable 200ms to 10 seconds |
| AUXILIARY | |
| Self powered | |
| WEIGHT&CASE | Approx 0.4kg. 55mm case |
Ordering Information |
| Product Code | Un Input | Freq | Option |
| M200-PB2 | 415V | 50Hz | Under volts at 70% |
Options |
| 1 | Adjustable time delay max 30 seconds |
| 2 | Internal under voltage set between 90% and 70% |
| 3 | Calibration at nominal Hz 35...450Hz |
| 4 | Calibration at temperature other than 23șC |
Data Sheet in PDF Format Available here