HomeProductsEnquiry FormContact UsThe CompanyQuality

 

Detailed Specifications

 

Performance

IMPEDANCE  
M300-VAD 10K Ohm/V
M300-VD1/2 > 100K Ohm
M300-VD3/4 10K Ohm/V
   
BURDEN  
M300-AAD < 2VA
M300-AD1/2/3/4 20mV drop
   
OVERLOAD  
Current 4 x continuous
  25 x 1 second
Voltage 1.5 x continuous
  4 x 1 second
Accuracy ± 0.05% of reading ± 1 digits
Resolution 0.05%
Linearity ± 1 digit roll over error ± 2 digits
Conversion Dual slope integration
CMR AC 50dB 50 to 60Hz
  DC 25 1K Ohm source unbalanced

Environmental & Insulation

Working Temperature 0-60 deg C
Function Temperature -25 to +70 deg C
Storage Temperature -55 to 85 deg C
Temperature Coefficient 0.01% per deg C
Relative Humidity 0-95% non-condensing
Warm up time 1 min
Shock 30g in 3 planes
Test Voltage 4kV RMS 50Hz 1 min

Auxiliary Power Supply

AC Voltage 115/230/400 Volts (±25%)
  45 to 65 Hz Burden < 2VA
DC Voltage 24/48/110 Volts (± 20%)
  Galvanic isolation. Burden < 3W

Display

Digits 1999 Full scale
Size 14.2mm (0.56") 7 segment red
Decimal Point Internally selectable
Overrange indication Displays "1" or "-1"
Update response time < 1 second
Polarity Automatic with (-) indicating negative inputs

Enclosure

DIN case Dimensions 96 x 48 x 98
Material Black Polycarbonate Complying with UL94VO
Terminals Screw type for 2 x 0.5-3.5mm
Weight 0.4kg
Enclosure code  IP 54 NEM A 12 Optional IP65 NEM A4

Wiring Diagram

DP-wiring2.gif (9870 bytes)

a) All inputs (AC or DC) are connected via terminals 1 & 3
b) All Auxiliary supplies (AC or DC) are connected via terminals 6 & 8
c) Access to the "ZERO" & "SPAN" adjustment. Remove terminal
  blanks in position 9 & 10. ZERO = 10,SPAN = 9
d) Optional externally selectable decimal point. 16=common, 15=1.999
  14 = 19.99, 13=199.9 Link 16 as required.

Dimensions

digital panel meter : dimensions

 

   
main digital panel meters page Main Digital Meters Page

Contact sales: sales@hobut.co.uk