16 Series Moulded Case Current Transformers

Description
A range of compact moulded case current transformers suitable for primary currents from 30A to 800A with built in sealable terminal covers.
Application
For transforming various primary currents into 5A or 1A standard secondary using 40 x 10mm, 30 x 10mm and 20 x 20mm busbars or cables up to 28mm diameter
Range, Ordering Information & Dimensions

TYPE 162
| Class 3 | Class 1 | Class 0.5 | |||||||
| VA | 1 | 1.5 | 2.5 | 1 | 1.5 | 2.5 | 1 | 1.5 | 2.5 |
| 30A | A1 | - | - | - | - | - | - | - | - |
| 40A | B1 | B2 | - | - | - | - | - | - | - |
| 50A | C1 | C2 | - | C4 | - | - | - | - | - |
| 60A | D1 | D2 | D3 | D4 | D5 | - | - | - | - |
| 80A | E1 | E2 | E3 | E4 | E5 | - | - | - | - |
TYPE 164
| Class 3 | Class 1 | Class 0.5 | |||||||
| VA | 2.5 | 5 | 10 | 2.5 | 5 | 10 | 2.5 | 5 | 10 |
| 100A | A1 | - | - | A4 | - | - | - | - | - |
| 150A | B1 | - | - | B4 | - | - | - | - | - |
| 200A | C1 | - | - | C4 | - | - | C7 | - | - |
| 250A | D1 | D2 | - | D4 | - | - | D7 | - | - |
| 300A | E1 | E2 | - | E4 | - | - | E7 | - | - |
| 400A | F1 | F2 | - | F4 | F5 | - | F7 | - | - |
| 500A | G1 | G2 | G3 | G4 | G5 | - | G7 | G8 | - |
| 600A | H1 | H2 | H3 | H4 | H5 | - | H7 | H8 | - |
| 800A | J1 | J2 | J3 | J4 | J5 | J6 | J7 | J8 | - |
1A secondary available by request.
Order Example: A moulded case current transformer type 164, with 5A secondary and 400A primary 5VA class 1 is part number 164-5-F5.
Technical Specification
- Conforms to IEC185, BS7626, BSEN 60044-1 and IEC 60044-1.
- Rated system voltage 0.72/3kV.
- Ambient temperature range -30ºC to 85ºC.
- Continuous current, 1.2 x rated current.
- Built in sealable terminal covers.
- Mounting Feet supplied.
- Narrow Width - 60mm.
- DIN Rail clip supplied as optional extra.