M560 Powersig complete with 3 analogue outputs

Description:

The M560 PowerSig is a complete 1 phase or 3 phase multifunction AC power transducer with 3 analogue outputs

Analogue Outputs

Upto 3 fully isolated outputs are available. Most of the parameters measured can be assigned to the outputs. Outputs can be either DC mA or DC volts. If PowerSig is purchased without the option of RS485 the user must specify which parameter is required for each output when ordering.

Parameters Measured

Phase voltage (V)
Line Voltage (V)
Phase Current (I)
Frequency (Hz)
Active Power Per Phase (W)
System Active Power (W)
Reactive Power per Phase (VAr)
System Reactive Power (V Ar)
Apparent Power per Phase (VA)
System Apparent Power (VA)
Import Active Energy (W.h)
Export Active Energy (W.h)
Import Reactive Energy (VAr.h)
Export Reactive Energy (VAr.h)
Apparent Energy (VA.h)
Ampere Energy (A.h)
Power Factor per Phase (P.F.)
System Power Factor (P.F.)
Amp Demand (Ad)
Watt Demand (Wd)
V A Demand (VAd)
Maximum Amp Demand (Max Ad)
Maximum Watt Demand Import (Max Wd)
Maximum Watt Demand Export (Max Wd)
Maximum VA Demand (Max VAd)
Neutral Current

Options

RS485 Output This is auto configurable and set up software is provided.
Pulsed Output This can be assigned to Wh, Varh, Ah or Vah
DC Auxiliary  
If RS485 output is not required. The customer should specify which parameter is required for analogue outputs, CT ratios, VT ratios, pulse duration etc. These can be programmed by out factory before despatch.

Ordering Information

Information Required Example
Product Code M560-AT9
Nominal Input Voltage 230 / 400V AC
Nominal Input Current 5A AC
System Frequency 50Hz
Auxiliary 230V
Output 3 x 4-20mA
Option RS485 Modbus

Specifications

ACCURACY INPUT
Specified @ 23șC 10%-Un 10%-ln Rated Un: Direct connected voltages between 57.8 and 600V. Specify Nominal
Paremeters unless stated: Class 0.3% to IEC 688 Range: 2-120% Un
Volts and Amps: Class 0.25% to IEC 688 Overload 1.5 x Un cont. 4 x Un for 1 sec
Frequency: Class: 0.1Hz o IEC 688 Rated In: 1 or 5 Amp
Power Factor: Class: 1.0% to IEC 688 Range 2-120% In
Active and Reactive Energy: 1% of reading IEC 1036 Burden: 0.5VA per phase Volts & Amps
Overload: 4 x In continous. 50 x In for 1 sec
Frequency 50/60Hz Nominal range 45/65Hz
ANALOGUE OUTPUTS APPLIED STANDARDS
3 Outputs: Programmable to any 3 parameters (Apart from energy measurements) General: IEC688 BSEN60688, BS4889, IEC359.
Rated value: Specified @ 20mA EMC:
0-1mA into < 10 kOhm load Emmisions: BSEN50081/1
0-5mA into < 2 kOhm load Immunity BSEN50082/2
0-10mA into < 1 kOhm load Safety: IEC 1010, BSEN601010
0-20mA into < 0.5 kOhm load
4-20mA into < 0.5 kOhm load
0-10 volts > 1 kOhm load
INSULATION
Test voltage: 4kV RMS 50 Hz for 1 min
Inputs / Case / Auxiliary / Output
3kV RS485 / Outputs
1.5kV relay
1kV between Outputs
Impulse Test: EMC 5kV transient coplies with IEC801/ EN55020 HF
Surge Withstand: IEC801/EN55020 Ansi C37.90A
Interference: EHF 2.5kV 1Mhz complying to IEC255-4
Protective class II: Complying to IEC348
ENVIRONMENT APPROVALS
Working temp: 0 - +60șC UL C-UL CSA
Storage temp: -30 - 65șC
Temp coefficient: 0.01% per șC
AUXILIARY
AC voltage 115 or 230 or 277 volts (± 15%)
DC voltage 12 / 24 / 48 / 110 / 125 volts (± 15%)

 

Case Dimensions

Connection Diagrams

Manual in PDF format available Here