HomeProductsEnquiry FormContact UsThe CompanyQuality

 

16 Series Moulded Case

Current Transformers
   
Description A range of compact moulded case current transformers suitable for primary currents from 30A to 800A with built in sealable terminal covers.
Application For transforming various primary currents into 5A or 1A standard secondary using 40 x 10mm, 30 x 10mm and 20 x 20mm busbars or cables up to 28mm diameter

Range,  Ordering Information & Dimensions

TYPE 162

  Class 3 Class 1 Class 0.5
VA 1 1.5 2.5 1 1.5 2.5 1 1.5 2.5
30A A1 - - - - - - - -
40A B1 B2 - - - - - - -
50A C1 C2 - C4 - - - - -
60A D1 D2 D3 D4 D5 - - - -
80A E1 E2 E3 E4 E5 - - - -

 

TYPE 164

  Class 3 Class 1 Class 0.5
VA 2.5 5 10 2.5 5 10 2.5 5 10
100A A1 - - A4 - - - - -
150A B1 - - B4 - - - - -
200A C1 - - C4 - - C7 - -
250A D1 D2 - D4 - - D7 - -
300A E1 E2 - E4 - - E7 - -
400A F1 F2 - F4 F5 - F7 - -
500A G1 G2 G3 G4 G5 - G7 G8 -
600A H1 H2 H3 H4 H5 - H7 H8 -
800A J1 J2 J3 J4 J5 J6 J7 J8 -
 
1A secondary available by request.

Order Example: A moulded case current transformer type 164, with 5A secondary and 400A primary 5VA class 1 is part number 164-5-F5.

 

Technical Specification

   
  •  
Conforms to IEC185, BS7626,  BSEN 60044-1 and IEC 60044-1.
  •  
Rated system voltage 0.72/3kV.
  •  
Ambient temperature range -30ºC to 85ºC.
  •  
Continuous current, 1.2 x rated current.
  •  
Built in sealable terminal covers.
  •  
Mounting Feet supplied.
  •  
Narrow Width - 60mm.
  •  
DIN Rail clip supplied as optional extra.

Data Sheet In PDF Format Available here

 

sales enquiry form

Sales Enquiry
hobut home page, panel meters, shunts, transformers and associated products Home
main current transformer page, ring type, moulded case, encapsulated Main Current Transformer Page

Contact sales: sales@hobut.co.uk